Western Reserve Controls WRC-CANR-DF-DN User Manual Page 17

  • Download
  • Add to my manuals
  • Print
  • Page
    / 31
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 16
Western Reserve Controls WRC-CANX-xx Series 3
PUB 14.0 User’s Manual
13
Important: Per the DeviceNet and SDS specs -- do not terminate devices on drop lines.
An appropriate terminating resistor kit, WRC part number RM121DN, which satisfies both DeviceNet
and SDS specs, is included with your Extender.
Note: The WRC-CANX Series 3 family is configured at the factory with 2 internal terminating
resistors on each network one for Network A and one for Network B using jumpers W1 and W2. If these
are used in a trunk line, no other terminators should be placed at the CANX that end of the network.
Note: If the CANX is used on a drop line, the internal terminating resistor should be removed on
Network A the drop line directly from the trunk line.